Commercial hood cleaning checklist: what a full job includes
A full commercial hood cleaning covers the hood, the plenum, the duct, and the rooftop fan, and ends with a tag, a report, and photos. Here is the checklist, in the order a crew works.

A full commercial hood cleaning has five parts: prep, the hood and plenum, the duct, the rooftop fan, and the paperwork. If any one is missing, it was not a full job.
Use this as a checklist the next morning. You do not need to watch the crew. You need to know what done looks like.
1. Before the crew starts
- Cooking equipment is off and cool.
- Appliances, prep surfaces, and the floor under the hood are covered in plastic.
- Pilot lights and gas are handled so nothing is lit under a tarp.
- The exhaust fan switch is locked out while people are working on it. NFPA 96 requires this.
- The crew has roof access. A key or a ladder location, sorted before midnight.
The plastic matters more than it looks. Degreaser and hot water run down, and a crew that skips the wrap leaves the mess on your flat-top.
2. The hood and filters
- Filters come out and get cleaned or swapped.
- The hood interior is scraped and degreased to bare metal.
- Grease cups and troughs are emptied and cleaned.
- The outside of the hood is wiped and polished.
This is the part everybody does, because it is the part you can see.
3. The plenum
- With the filters out, the chamber behind them is scraped and washed to bare metal.
- The duct opening at the top of the plenum is cleaned as far as the crew can reach from below.
The plenum is the first place an inspector looks, because it only takes pulling one filter. A brown film back there means the job stopped at the hood.
4. The duct
- Every access panel on the duct run is opened.
- The duct is scraped and washed from each opening, section by section.
- Panels go back on with their gaskets, sealed tight.
- Any section that could not be reached is written down.
This is where cheap jobs fall apart. A long horizontal run with no access cannot be cleaned by anyone, and an honest crew says so in writing. The fix is an access panel. More on why this matters in kitchen exhaust cleaning vs hood cleaning.
5. The rooftop fan
- Someone goes on the roof. Every time.
- The fan is tipped open on its hinge and cleaned inside: the bowl, the blades, the base.
- The belt and bearings get a look while it is open.
- The grease containment around the fan is checked and emptied.
- The fan is closed, the switch is unlocked, and the fan is run to confirm it works.
No hinge on the fan? Then it has to be unbolted and lifted, which is how wiring gets torn. NFPA 96 requires access to rooftop fans for cleaning, and a hinge kit is the usual answer.
6. Cleanup
- Plastic comes down and leaves with the crew.
- Floors are mopped. Walls behind the line are wiped.
- Filters are back in, all of them, no gaps.
- Pilots are relit and the equipment is back where it was.
The opening cook should walk in and not be able to tell anyone was there, except that the hood is clean.
7. The paperwork
- A tag on the hood. Company name, address, phone, and the date of service. The fire code requires it.
- A written report. Who did the work, what was done, when, and any areas not cleaned.
- Before and after photos. Plenum, duct, and fan. Not just the hood.
- The next due date. Set to how you cook.
Keep all of it at the restaurant. What each line on the certificate means is in our guide to what a hood cleaning certificate must show, and the intervals are in the Oregon fire code guide.
The five minute check the next morning
- Pull one filter. Is the plenum bare metal?
- Is there a new tag with yesterday's date?
- Does the fan run, and does it sound the same or better?
- Did you get photos of the duct and the fan?
- Does the report list anything as not cleaned?
Five yes answers and you got what you paid for. A no on the photos or the plenum is worth a phone call that day.
Frequently asked questions
What is included in a commercial hood cleaning?
A full job covers the hood and filters, the plenum behind the filters, the entire duct run, and the rooftop exhaust fan, followed by cleanup, a dated tag on the hood, a written report, and before and after photos.
How long does a commercial hood cleaning take?
It depends on the number of hoods, the length of the duct, and how much grease is in the system. Most single-hood restaurants are done overnight, between close and morning prep.
Should the cleaning crew go on the roof?
Yes. The exhaust fan sits on the roof and has to be opened and cleaned inside. A job done entirely from the kitchen did not clean the fan.
What should I check after a hood cleaning?
Pull a filter and look at the plenum, look for a new dated tag, confirm the fan runs, and ask for photos of the duct and fan along with the written report.
Want a crew that works this checklist every time? Get a free estimate or call (800) 973-5573 any hour.
Sources
- NFPA 96, Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations, Chapter 12
- International Fire Code Section 606.3.3 (inspection, cleaning, records and tags), as adopted in the 2025 Oregon Fire Code
- Oregon State Fire Marshal, Oregon Fire Code page (2025 Oregon Fire Code, effective October 1, 2025)