What Salem fire inspectors look for in a restaurant kitchen
Salem kitchens are inspected under the Oregon Fire Code. The hood tag, the cleaning records, the suppression system, and the walk-through items to have ready before anyone knocks.

In a Salem restaurant kitchen, a fire inspector is checking that the exhaust system is cleaned on schedule and tagged, that the hood's suppression system has been serviced, and that the cleaning records are on site. Everything else is the standard walk-through: exits, extinguishers, electrical.
Salem does not have a separate hood cleaning policy the way Portland does. The rules come straight from the Oregon Fire Code. Here is what that looks like at your back door.
Who inspects restaurants in Salem?
The Salem Fire Department enforces the fire code inside the city. The department's business office is at 370 Trade St. SE and can be reached at 503-588-6245.
The code they work from is the 2025 Oregon Fire Code, which took effect statewide on October 1, 2025 [1]. Kitchen exhaust is covered in Section 606. If you want the full breakdown, read our Oregon fire code guide.
What does the inspector check on the hood?
Four things, and they take about two minutes.
- The tag. The code requires a tag on the hood with the service company's name, address, phone number, and the date of service. The inspector reads the date first.
- The interval. Does that date fit how you cook? Every three months for charbroiling, woks, or 24-hour cooking. Every six months for most restaurants. Monthly for solid fuel. Yearly for low-volume kitchens.
- The system itself. Filters in place, no gaps. Then a filter comes out and they look at the plenum behind it.
- The records. A written report naming who did the work, what was done, and when.
A current tag over a brown plenum is the finding nobody wants. The tag says the system was cleaned. The plenum says otherwise.
What about the suppression system?
This is the nozzles and the pull station, and it is a different job from hood cleaning. The fire code requires the hood's extinguishing system to be serviced every six months by a licensed contractor, and after any time it discharges. It gets its own tag.
The inspector will look for that tag, check that the nozzles sit over the appliances they are meant to protect, and check that nothing is blocking the manual pull. If you moved a fryer since the last service, say so to your suppression company before the inspector notices.
They will also look for a Class K extinguisher near the line. That is the one rated for cooking oil fires.
What is The Compliance Engine?
It is how Salem collects service records. Under a City of Salem rule, contractors who service, inspect, or test fire protection systems in the city have to file their reports through a third-party repository called The Compliance Engine. Reports are due within 30 days of the work [2].
The rule covers systems that detect fire, sound alarms, or extinguish fire. That definition fits a hood suppression system. It does not name hood cleaning.
What this means for you: the fire department can already see whether your suppression service is current before anyone visits. Use a contractor who files. And keep your own copies on site anyway, because the hood cleaning report is still yours to produce.
The rest of the walk-through
The kitchen is one part of the visit. These are the items fire inspectors check in nearly every commercial building, and the ones restaurants trip on:
- Exits and the paths to them clear. The back hallway is not storage.
- Exit signs lit.
- Extinguishers mounted, visible, and serviced within the year.
- Clear space in front of the electrical panel.
- No extension cords doing the job of permanent wiring.
- Address numbers visible from the street.
What to have ready
Put it in one folder at the restaurant, where the manager on duty can find it.
- The latest hood cleaning certificate and report.
- Before and after photos of the plenum, the duct, and the fan.
- The date of your next cleaning.
- The suppression system service report.
- The extinguisher service tags, checked for dates.
What belongs on the certificate is in our guide to what a hood cleaning certificate must show.
If you get written up
A hood finding usually comes with a date to have it fixed by. Call the inspector, ask exactly what they want to see, and book a full-system cleaning that day. The step-by-step is in our guide on what to do after a failed hood inspection.
Salem is home for us. Our shop is on State Street, so a Salem kitchen with a deadline is a same-week job. See hood cleaning in Salem or Keizer.
Frequently asked questions
Who does fire inspections for restaurants in Salem, Oregon?
The Salem Fire Department enforces the Oregon Fire Code inside the city. The business office is at 370 Trade St. SE, 503-588-6245.
How often does a Salem restaurant need its hood cleaned?
Salem follows the Oregon Fire Code intervals: every six months for most restaurants, every three months for charbroiling, wok, or 24-hour cooking, monthly for solid fuel, and yearly for low-volume kitchens.
Does Salem have its own hood cleaning rules like Portland?
No. Portland has a separate policy, FIR-8.08. Salem enforces the Oregon Fire Code as written, which requires scheduled inspection, cleaning when grease is found, a tag on the hood, and written records.
Is hood cleaning the same as the suppression system inspection?
No. Hood cleaning removes grease from the hood, duct, and fan. The suppression system is the nozzles and pull station, serviced every six months by a licensed fire protection contractor. Each gets its own tag.
Inspection coming up in Salem or Keizer? Get a free estimate with the date in the notes, or call (800) 973-5573 any hour.
Sources
- Oregon State Fire Marshal, Oregon Fire Code page (2025 Oregon Fire Code, effective October 1, 2025)
- City of Salem administrative rule 105-002, single-point repository for fire protection system records
- City of Salem, Salem Fire Department contact information
- International Fire Code Sections 606.3.3 and 904 (hood cleaning records and tags, extinguishing system service), as adopted in the 2025 Oregon Fire Code